Page 19 - North American Clean Energy May June 2018 Issue
P. 19
solar power
Setting the Standard
PRC-024-2 & LVRT requirements – di erentiation between internal and external faults in wind and solar farms
e result of these simulations shows that
this rapid impedance change, made by the combined circuit breaker and high-speed grounding switch (VDH/GSMI) as a feeder breaker, can help design engineers provide PRC- 024-2’s required functionality and protection systems by making it easier to di erentiate between Internal and External Faults.
is special feeder breaker signals the generators that the fault is inside the plant,
and shuts them down when under-voltage
ride through is not necessary. is provides a valuable discriminatory function that regular MV circuit breakers do not.
e balanced three-phases short to ground, caused by VDH/GSMI, dropping voltage to zero at that point, should be treated as a shutdown signal. is signal starts at the substation,
and goes through the power cables to all the generators of the collection circuit - faster and safer than any other means - and gets to all of the connected generators at the same time.
By measuring voltage at generator terminals, it’s possible to identify a fault outside the plant and keep generating power, while complying with PRC-024-2.
Augusto X. Morando is a Sales Engineer at EMA Electromechanics. EMA was founded in 1952 in Buenos Aires Argentina, supplying low, medium and high voltage apparatus to major utility companies throughout Latin America. Product innovation and continuous growth in the electrical market led to EMA’s expansion into the North American market.
EMA Electromechanics
www.emaelectromechanics.com
by Augusto Morando
Hybrid inverter for residential solar power backup applications
Based on Delta's transformer-less (TL) solar inverter series, the residential E-Series consists of the E6, E8, and E10 models, which have maximum output power levels of 6,000VA, 8,000VA, and 10,000VA. ese Delta systems with built-in solar inverters integrate power conditioning capabilities for power back-up applications, and can supply power directly to the home, grid, or energy storage systems. e E-Series
is compatible with both DC and AC coupled for
high- and low-voltage batteries, as well as standalone applications. With the ability to support a wide variety battery backup systems and prede ned energy management applications, the E-Series increases
the ROI of a homeowner's entire solar system. With Bluetooth and Wi-Fi compatibility, as well as a user- friendly human machine interface (HMI), the E-Series supports cloud-based data collecting, provides transparency into system operations, and is capable
of performing remote rmware upgrades, reducing
the need for on-site support visits. Simple wiring creates a quick and easy installation experience,
taking 15 minutes from start to nish, including
system con guration. Designed in compliance with UL1741SA testing to ful ll HECO and California Rule 21 conditions, the E Series is able to e ectively operate in the smart grid environment. e E series also o ers a high accuracy, integrated optional revenue grade meter (RGM) that complies with ANSI standards.
Delta Group | www.deltaww.com
for di erentiation between internal and external faults, and that is what VDH/ GSMI provides.
In order to study the FERC PRC-024- 2 requirement e ectively, a PSCAD tool was used to simulate how the voltage would behave at the mains of the Generator in a farm equipped with VDH/GSMI – rst, in the presence of an External Fault, and second, in the presence of an Internal Fault. (Figure 2)
For our External Fault simulation, we will consider that voltage will drop instantaneously to zero at POI for a period of 150 ms. (Figure 3)
When an External Fault happens, there is voltage drop at the terminals of the Generators (in our PSCAD model, that drop was 83%). After 150 ms the fault disappears. Although 83% is a huge drop, it is not as robust as the voltage drop caused by the combined circuit breaker and high-speed grounding switch (VDH/ GSMI) tripped during an Internal Fault.
Simulating an Internal Fault, the combined circuit breaker and high- speed grounding switch (VDH/GSMI) trips, opens the feeder circuit, clears the fault, and, in less than a cycle, makes a balanced three-phases short to ground on the collection circuit. is causes a robust voltage drop at the terminals of each generator unit. (Figure 4)
In case of an Internal Fault, in our PSCAD modeled farm, the voltage measured at the terminals of the Generators dropped more than 90%.
e di erence in voltage drops between Internal and External faults
is given by the impedance of the main plant power transformer. In both cases the system is in presence of zero volt; in one case said zero volt is outside the farm (External Fault), and on the other case on the collection circuit (Internal Fault).
Figures 5 and 6 show voltage drop on a per-unit basis. In Figure 5, the voltage drop is measured at the terminals of the Generator, caused by a voltage drop to zero for a period of 150 ms at POI (External Fault). In Figure 6, the voltage drop is caused by the action of VDH/ GSMI after clearing the Internal Fault. Figure 7 is an overlap of gures 5 and
6, showing the di erence of voltage drop at the terminals of the Generators. At near full power for the wind or
solar power plant, the delta in voltage between the two fault locations is 8%,
a clear signal for the Generators to stay online, or shut down.
Figure 2: Faults locations for PSCAD simulations in a Wind or Solar Power plant using VDH/GSMI.
Figure 6: Voltage drop measured at the terminals of the Generator, caused by the fast action of VDH/GSMI after clearing the fault.
Figure 5: Voltage drop at the generator terminals subjected to an External Fault.
THE FEDERAL ENERGY REGULATORY COMMISSION (FERC) APPROVED
Reliability Standard PRC-024-2; this standard requires power plants to set their relays so that the plant remains connected during power spikes. PRC-024-2 ensures that plant owners set their generator protective relays so that generating units remain connected during de ned voltage excursions, including the operation for 9 cycles (150 ms) at zero voltage, measured at POI (Point Of Interconnection). In other words, protection relays must not trip the generators within the “no trip zone” for faults happening at POI, or beyond the wind or solar plant. (Figure 1)
POI means the transmission side starting on the high voltage side of the substation main transformer of a wind or solar power plant substation.
In order to comply with the standard, power generation asset owners have been resetting their protection relay of their wind and solar power plants. But faults also happen inside the wind or solar farm, so there is a need
Figure 7: Comparative of voltage drop at the generator terminals – Amplified overlap of Figure 5 and 6.
Figure 1: Voltage Ride-Through Time Duration Curve.
Figure 3: External Fault location (top) and Voltage measured at the mains of the Generator (bottom).
PHLEGON® SINGLE AXIS TRACKER
Lowest Installed and O&M Costs for the Harshest Conditions
June September October November December All year 20-21 24-27 19-20 13-14 13-14 round
Visit us in
GP JOULE is a global renewable energy company with an extensive track record in commercial and utility-scale ground mount PV. Our proprietary PHLEGON® single axis tracker, designed for northern climates and challenging sites, comes with a complete offering of engineering,
installation and commissioning services. Learn more at www.gp-joule.com.
VisitusatSolarCanada BOOTH719
Ad-GPJOUMLEA-4Y8•7J5Ux3N50E0-20404128018/./in/ddw1ww.nacleanenergy.com 36
04/04/2018
20:50
North American Clean Energy
37
Figure 4: Internal Fault location (top) and Voltage measured at the mains of the Generators in a farm equipped with VDH/GSMI (bottom).
Utility Size Panel Washing
And Snow Removal
Wash up to 14,000 panels/shift 59HP Kubota Turbo diesel Brush length up to 14 ft
Remove snow from up to 16,000 panels/shift
[email protected]
640 gallon tank
CANADA: 780-905-9762
USA: 203-637-1900
Calgary
Anaheim
Chicago Minneapolis
New York
Toronto